(COPPER CONDUCTORS) BS7889 BS7211 GB12706.3
CURRENT CARRYING CAPACITY (Amperes):Ambient temperature: 30oC
Conductor operating temperature: 90oC
APPENDIX 3
Table 3(a)
Conductor
Cross-Sectional Area |
Enclosed
in conduit in thermally insulating wall etc. |
Enclosed in conduit on a wall or in trunking etc. |
Cipped
direct |
On
a perforated cable tray horizontal or vertical |
Free
air |
|||||||
|
|
|
|
|
|
|||||||
|
|
|||||||||||
2
cables, Single-Phase a.c. or d.c. |
3
or 4 cables three-phase a.c. |
2
cables, Single-Phase a.c. or d.c. |
3
or 4 cables three-phase a.c. |
2
cables, Single-Phase a.c. or d.c. flat and touching |
3 or 4 cables three-phase a.c. flat and touching or trefoil |
2
cables, Single-Phase a.c. or d.c. flat and touching |
3
or 4 cables three-phase a.c. flat and touching or trefoil |
2 cables, Single-Phase a.c. or d.c., or 3 cables three-phase |
2
cables, Single-Phase a.c. or d.c., or 3 cables three-phase |
3
cables trefoil, three-phase a.c. |
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
|
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
|
1 |
14 |
13 |
17 |
15 |
19 |
17.5 |
- |
- |
- |
- |
- |
|
1.5 |
18 |
17 |
22 |
19 |
25 |
23 |
- |
- |
- |
- |
- |
|
2.5 |
24 |
23 |
30 |
26 |
34 |
31 |
- |
- |
- |
- |
- |
|
4 |
33 |
30 |
40 |
35 |
46 |
41 |
- |
- |
- |
- |
- |
|
6 |
43 |
39 |
51 |
45 |
59 |
54 |
- |
- |
- |
- |
- |
|
10 |
58 |
53 |
71 |
63 |
81 |
74 |
- |
- |
- |
- |
- |
|
16 |
76 |
70 |
95 |
85 |
109 |
99 |
- |
- |
- |
- |
- |
|
25 |
100 |
91 |
126 |
111 |
143 |
130 |
158 |
140 |
183 |
163 |
138 |
|
35 |
124 |
111 |
156 |
138 |
176 |
161 |
195 |
176 |
226 |
203 |
171 |
|
50 |
149 |
135 |
189 |
168 |
228 |
209 |
239 |
215 |
274 |
246 |
209 |
|
70 |
189 |
170 |
240 |
214 |
293 |
268 |
308 |
279 |
351 |
318 |
270 |
|
95 |
228 |
205 |
290 |
259 |
355 |
326 |
375 |
341 |
426 |
389 |
330 |
|
120 |
263 |
235 |
336 |
299 |
413 |
379 |
436 |
398 |
495 |
453 |
385 |
|
150 |
300 |
270 |
375 |
328 |
476 |
436 |
505 |
461 |
570 |
524 |
445 |
|
185 |
341 |
306 |
426 |
370 |
545 |
500 |
579 |
530 |
651 |
600 |
511 |
|
240 |
400 |
358 |
500 |
433 |
644 |
590 |
686 |
630 |
769 |
711 |
606 |
|
300 |
459 |
410 |
573 |
493 |
743 |
681 |
794 |
730 |
886 |
824 |
701 |
|
400 |
- |
- |
683 |
584 |
868 |
793 |
915 |
849 |
1065 |
994 |
820 |
|
500 |
- |
- |
783 |
666 |
990 |
904 |
1044 |
973 |
1228 |
1150 |
936 |
|
630 |
- |
- |
900 |
764 |
1130 |
1033 |
1191 |
1115 |
1423 |
1338 |
1069 |
|
800 |
- |
- |
- |
- |
1288 |
1179 |
1358 |
1275 |
1581 |
1485 |
1214 |
|
1000 |
- |
- |
- |
- |
1443 |
1323 |
1520 |
1436 |
1775 |
1671 |
1349 |
|
Where
a conductor operates at a temperature exceeding 90oC it shall
be ascertained that the equipment connected to the conductor is suitable
for the conductor operating temperature.
Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 90oC. the current rating given in the equivalent table for 90oC thermosetting insulated cables (BS 7889, BS 7211) shall be used.
The current carrying capacity in columns 2 to 5 are also applicable to flexible cable to BS 7211 table 3(b) where the cables are used in fixed insulation.
For details, please refer to BS7671:2001 Table 4E1A
VOLTAGE DROP (per ampere per metre):Conductor operating temperature: 90oC
Table 3(b)
Conductor
Cross-Sectional Area |
2
cables d.c. |
2
cables single phase a.c. |
3
or 4 cables three phase a.c. |
|
|||||||||||||||||||
Enclosed
in conduit etc. in or on a wall |
Clipped
direct or on trays, touching |
Spaced1 |
Enclosed
in conduit etc. in or on a wall |
In
trefoil |
Flat
touching |
Flat
Spaced* |
|
||||||||||||||||
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|||||||||||||||||
|
|
||||||||||||||||||||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|
||||||||||||||
1 |
46 |
46 |
46 |
46 |
40 |
40 |
40 |
40 |
|
||||||||||||||
1.5 |
31 |
31 |
31 |
31 |
27 |
27 |
27 |
27 |
|
||||||||||||||
2.5 |
19 |
19 |
19 |
19 |
16 |
16 |
16 |
16 |
|
||||||||||||||
4 |
12 |
12 |
12 |
12 |
10 |
10 |
10 |
10 |
|
||||||||||||||
6 |
7.9 |
7.9 |
7.9 |
7.9 |
6.8 |
6.8 |
6.8 |
6.8 |
|
||||||||||||||
10 |
4.7 |
4.7 |
4.7 |
4.7 |
4.0 |
4.0 |
4.0 |
4.0 |
|
||||||||||||||
16 |
2.9 |
2.9 |
2.9 |
2.9 |
2.5 |
2.5 |
2.5 |
2.5 |
|
||||||||||||||
|
|
r |
x |
z |
r |
x |
z |
r |
X |
z |
r |
X |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
|
25 |
1.85 |
1.85 |
0.31 |
1.90 |
1.85 |
0.190 |
1.85 |
1.85 |
0.28 |
1.85 |
1.60 |
0.27 |
1.65 |
1.60 |
0.165 |
1.60 |
1.60 |
0.190 |
1.60 |
1.60 |
0.27 |
1.60 |
|
35 |
1.35 |
1.35 |
0.29 |
1.35 |
1.35 |
0.180 |
1.35 |
1.35 |
0.27 |
1.35 |
1.15 |
0.25 |
1.15 |
1.15 |
0.155 |
1.15 |
1.15 |
0.180 |
1.15 |
1.15 |
0.26 |
1.20 |
|
50 |
0.99 |
1.00 |
0.29 |
1.05 |
0.99 |
0.180 |
1.00 |
0.99 |
0.27 |
1.00 |
0.87 |
0.25 |
0.90 |
0.86 |
0.155 |
0.87 |
0.86 |
0.180 |
0.87 |
0.86 |
0.26 |
0.89 |
|
70 |
0.68 |
0.70 |
0.28 |
0.75 |
0.68 |
0.175 |
0.71 |
0.68 |
0.26 |
0.73 |
0.60 |
0.24 |
0.65 |
0.59 |
0.150 |
0.61 |
0.59 |
0.175 |
0.62 |
0.59 |
0.25 |
0.65 |
|
95 |
0.49 |
0.51 |
0.27 |
0.58 |
0.49 |
0.170 |
0.52 |
0.49 |
0.26 |
0.56 |
0.44 |
0.23 |
0.50 |
0.43 |
0.145 |
0.45 |
0.43 |
0.170 |
0.46 |
0.43 |
0.25 |
0.49 |
|
120 |
0.39 |
0.41 |
0.26 |
0.48 |
0.39 |
0.165 |
0.43 |
0.39 |
0.25 |
0.47 |
0.35 |
0.23 |
0.42 |
0.34 |
0.140 |
0.37 |
0.34 |
0.165 |
0.38 |
0.34 |
0.24 |
0.42 |
|
150 |
0.32 |
0.33 |
0.26 |
0.43 |
0.32 |
0.165 |
0.36 |
0.32 |
0.25 |
0.41 |
0.29 |
0.23 |
0.37 |
0.28 |
0.140 |
0.31 |
0.28 |
0.165 |
0.32 |
0.28 |
0.24 |
0.37 |
|
185 |
0.25 |
0.27 |
0.26 |
0.37 |
0.26 |
0.165 |
0.30 |
0.25 |
0.25 |
0.36 |
0.23 |
0.23 |
0.32 |
0.22 |
0.140 |
0.26 |
0.22 |
0.165 |
0.28 |
0.22 |
0.24 |
0.33 |
|
240 |
0.19 |
0.21 |
0.26 |
0.33 |
0.20 |
0.160 |
0.25 |
0.195 |
0.25 |
0.31 |
0.185 |
0.22 |
0.29 |
0.170 |
0.140 |
0.22 |
0.170 |
0.165 |
0.24 |
0.170 |
0.24 |
0.29 |
|
300 |
0.155 |
0.175 |
0.25 |
0.31 |
0.160 |
0.160 |
0.22 |
0.155 |
0.25 |
0.29 |
0.150 |
0.22 |
0.27 |
0.140 |
0.140 |
0.195 |
0.135 |
0.160 |
0.21 |
0.135 |
0.24 |
0.27 |
|
400 |
0.120 |
0.140 |
0.25 |
0.29 |
0.130 |
0.155 |
0.20 |
0.125 |
0.24 |
0.27 |
0.125 |
0.22 |
0.25 |
0.110 |
0.135 |
0.175 |
0.110 |
0.160 |
0.195 |
0.110 |
0.24 |
0.26 |
|
500 |
0.093 |
0.120 |
0.25 |
0.28 |
0.105 |
0.155 |
0.185 |
0.098 |
0.24 |
0.26 |
0.100 |
0.22 |
0.24 |
0.090 |
0.135 |
0.160 |
0.088 |
0.160 |
0.180 |
0.085 |
0.24 |
0.25 |
|
630 |
0.072 |
0.100 |
0.25 |
0.27 |
0.086 |
0.155 |
0.175 |
0.078 |
0.24 |
0.25 |
0.088 |
0.21 |
0.23 |
0.074 |
0.135 |
0.150 |
0.071 |
0.160 |
0.170 |
0.068 |
0.23 |
0.24 |
|
800 |
0.056 |
- |
0.072 |
0.150 |
0.170 |
0.064 |
0.24 |
0.25 |
- |
0.062 |
0.130 |
0.145 |
0.059 |
0.155 |
0.165 |
0.055 |
0.23 |
0.24 |
|
||||
1000 |
0.045 |
- |
0.063 |
0.150 |
0.165 |
0.054 |
0.24 |
0.24 |
- |
0.055 |
0.130 |
0.140 |
0.050 |
0.155 |
0.165 |
0.047 |
0.23 |
0.24 |
|
Note:
1. Spacings larger than current dimension, it will result a larger
voltage drop.
Correction
Factors for Sizing of Cable Conductors
(1)Correction factors for ambient temperature
APPENDIX 1
Table 1(a)
Type
of insulation |
Operating
temperature |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
75 |
80 |
85 |
90 |
95 |
|
|||
General
purpose PVC |
70oC |
1.03 |
1.0 |
0.94 |
0.87 |
0.79 |
0.71 |
0.61 |
0.50 |
0.35 |
- |
- |
- |
- |
- |
- |
|
|
|
||||||||||||||||||
Heat
resisting PVC |
90oC |
1.03 |
1.0 |
0.97 |
0.94 |
0.91 |
0.87 |
0.84 |
0.80 |
0.76 |
0.71 |
0.61 |
0.50 |
0.35 |
- |
- |
||
Thermosetting
(XLPE) |
90oC |
1.02 |
1.0 |
0.96 |
0.91 |
0.87 |
0.82 |
0.76 |
0.71 |
0.65 |
0.58 |
0.50 |
0.41 |
0.29 |
- |
- |
|
|
|
Note: 1.For details, please refer to BS7671:2001 Tale 4C1