Power Cable-Technical Details

Single core thermosetting insulated cables, with or without sheath

(COPPER CONDUCTORS) BS7889  BS7211  GB12706.3

CURRENT CARRYING CAPACITY (Amperes):Ambient temperature: 30oC

                                                                                      Conductor operating temperature: 90oC

APPENDIX 3

Table 3(a) 

Conductor Cross-Sectional Area

Enclosed in conduit in thermally insulating wall etc.

Enclosed in conduit on a wall or in trunking etc.

Cipped direct

On a perforated cable tray horizontal or vertical

Free air

2 cables, Single-Phase a.c. or d.c.

3 or 4 cables three-phase a.c.

2 cables, Single-Phase a.c. or d.c.

3 or 4 cables three-phase a.c.

2 cables, Single-Phase a.c. or d.c. flat and touching

3 or 4 cables three-phase a.c. flat and touching or trefoil

2 cables, Single-Phase a.c. or d.c. flat and touching

3 or 4 cables three-phase a.c. flat and touching or trefoil

2 cables, Single-Phase a.c. or d.c., or 3 cables three-phase

2 cables, Single-Phase a.c. or d.c., or 3 cables three-phase

3 cables trefoil, three-phase a.c.

 

1

2

3

4

5

6

7

8

9

10

11

12

 

mm2

A

A

A

A

A

A

A

A

A

A

A

 

1

14

13

17

15

19

17.5

-

-

-

-

-

 

1.5

18

17

22

19

25

23

-

-

-

-

-

 

2.5

24

23

30

26

34

31

-

-

-

-

-

 

4

33

30

40

35

46

41

-

-

-

-

-

 

6

43

39

51

45

59

54

-

-

-

-

-

 

10

58

53

71

63

81

74

-

-

-

-

-

 

16

76

70

95

85

109

99

-

-

-

-

-

 

25

100

91

126

111

143

130

158

140

183

163

138

 

35

124

111

156

138

176

161

195

176

226

203

171

 

50

149

135

189

168

228

209

239

215

274

246

209

 

70

189

170

240

214

293

268

308

279

351

318

270

 

95

228

205

290

259

355

326

375

341

426

389

330

 

120

263

235

336

299

413

379

436

398

495

453

385

 

150

300

270

375

328

476

436

505

461

570

524

445

 

185

341

306

426

370

545

500

579

530

651

600

511

 

240

400

358

500

433

644

590

686

630

769

711

606

 

300

459

410

573

493

743

681

794

730

886

824

701

 

400

-

-

683

584

868

793

915

849

1065

994

820

 

500

-

-

783

666

990

904

1044

973

1228

1150

936

 

630

-

-

900

764

1130

1033

1191

1115

1423

1338

1069

 

800

-

-

-

-

1288

1179

1358

1275

1581

1485

1214

 

1000

-

-

-

-

1443

1323

1520

1436

1775

1671

1349

 

  1. Where a conductor operates at a temperature exceeding 90oC it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.

  2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 90oC.  the current rating given in the equivalent table for 90oC thermosetting insulated cables (BS 7889, BS 7211) shall be used.

  3. The current carrying capacity in columns 2 to 5 are also applicable to flexible cable to BS 7211 table 3(b) where the cables are used in fixed insulation.

  4. For details, please refer to BS7671:2001 Table 4E1A

 

VOLTAGE DROP (per ampere per metre):Conductor operating temperature: 90oC  

Table 3(b) 

Conductor Cross-Sectional Area

2 cables d.c.

2 cables single phase a.c.

3 or 4 cables three phase a.c.

 

Enclosed in conduit etc. in or on a wall

Clipped direct or on trays, touching

Spaced1

Enclosed in conduit etc. in or on a wall

In trefoil

Flat touching

Flat Spaced*

 

     

 

 

 

 

 

 

 

    

 

 

 

 

 

 

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

 

1

46

46

46

46

40

40

40

40

 

1.5

31

31

31

31

27

27

27

27

 

2.5

19

19

19

19

16

16

16

16

 

4

12

12

12

12

10

10

10

10

 

6

7.9

7.9

7.9

7.9

6.8

6.8

6.8

6.8

 

10

4.7

4.7

4.7

4.7

4.0

4.0

4.0

4.0

 

16

2.9

2.9

2.9

2.9

2.5

2.5

2.5

2.5

 

 

 

r

x

z

r

x

z

r

X

z

r

X

z

r

x

z

r

x

z

r

x

z

 

25

1.85

1.85

0.31

1.90

1.85

0.190

1.85

1.85

0.28

1.85

1.60

0.27

1.65

1.60

0.165

1.60

1.60

0.190

1.60

1.60

0.27

1.60

 

35

1.35

1.35

0.29

1.35

1.35

0.180

1.35

1.35

0.27

1.35

1.15

0.25

1.15

1.15

0.155

1.15

1.15

0.180

1.15

1.15

0.26

1.20

 

50

0.99

1.00

0.29

1.05

0.99

0.180

1.00

0.99

0.27

1.00

0.87

0.25

0.90

0.86

0.155

0.87

0.86

0.180

0.87

0.86

0.26

0.89

 

70

0.68

0.70

0.28

0.75

0.68

0.175

0.71

0.68

0.26

0.73

0.60

0.24

0.65

0.59

0.150

0.61

0.59

0.175

0.62

0.59

0.25

0.65

 

95

0.49

0.51

0.27

0.58

0.49

0.170

0.52

0.49

0.26

0.56

0.44

0.23

0.50

0.43

0.145

0.45

0.43

0.170

0.46

0.43

0.25

0.49

 

120

0.39

0.41

0.26

0.48

0.39

0.165

0.43

0.39

0.25

0.47

0.35

0.23

0.42

0.34

0.140

0.37

0.34

0.165

0.38

0.34

0.24

0.42

 

150

0.32

0.33

0.26

0.43

0.32

0.165

0.36

0.32

0.25

0.41

0.29

0.23

0.37

0.28

0.140

0.31

0.28

0.165

0.32

0.28

0.24

0.37

 

185

0.25

0.27

0.26

0.37

0.26

0.165

0.30

0.25

0.25

0.36

0.23

0.23

0.32

0.22

0.140

0.26

0.22

0.165

0.28

0.22

0.24

0.33

 

240

0.19

0.21

0.26

0.33

0.20

0.160

0.25

0.195

0.25

0.31

0.185

0.22

0.29

0.170

0.140

0.22

0.170

0.165

0.24

0.170

0.24

0.29

 

300

0.155

0.175

0.25

0.31

0.160

0.160

0.22

0.155

0.25

0.29

0.150

0.22

0.27

0.140

0.140

0.195

0.135

0.160

0.21

0.135

0.24

0.27

 

400

0.120

0.140

0.25

0.29

0.130

0.155

0.20

0.125

0.24

0.27

0.125

0.22

0.25

0.110

0.135

0.175

0.110

0.160

0.195

0.110

0.24

0.26

 

500

0.093

0.120

0.25

0.28

0.105

0.155

0.185

0.098

0.24

0.26

0.100

0.22

0.24

0.090

0.135

0.160

0.088

0.160

0.180

0.085

0.24

0.25

 

630

0.072

0.100

0.25

0.27

0.086

0.155

0.175

0.078

0.24

0.25

0.088

0.21

0.23

0.074

0.135

0.150

0.071

0.160

0.170

0.068

0.23

0.24

 

800

0.056

-

0.072

0.150

0.170

0.064

0.24

0.25

-

0.062

0.130

0.145

0.059

0.155

0.165

0.055

0.23

0.24

 

1000

0.045

-

0.063

0.150

0.165

0.054

0.24

0.24

-

0.055

0.130

0.140

0.050

0.155

0.165

0.047

0.23

0.24

 

Note:   1. Spacings larger than current dimension, it will result a larger voltage drop.

             2.For details, please refer to BS7671:2001 Table 4E1B

 

Correction Factors for Sizing of Cable Conductors

(1)Correction factors for ambient temperature

APPENDIX 1

Table 1(a) 

Type of insulation

Operating temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

 

General purpose PVC

70oC

1.03

1.0

0.94

0.87

0.79

0.71

0.61

0.50

0.35

-

-

-

-

-

-

 

 

Heat resisting PVC

90oC

1.03

1.0

0.97

0.94

0.91

0.87

0.84

0.80

0.76

0.71

0.61

0.50

0.35

-

-

 
 

Thermosetting (XLPE)

90oC

1.02

1.0

0.96

0.91

0.87

0.82

0.76

0.71

0.65

0.58

0.50

0.41

0.29

-

-

 

 

Note:       1.For details, please refer to BS7671:2001 Tale 4C1

 