Power Cable-Technical Details

Multicore non-armoured XLPE insulated cables current rating

CURRENT CARRYING CAPACITY (Amperes):Ambient temperature: 30oC

                                                                                        Conductor operating temperature: 90oC

APPENDIX 5

Table 5(a) 

Conductor Cross-Sectional Area

Enclosed in conduit in thermally insulating wall etc.

Enclosed in conduit on a wall or in trunking etc.

Open and Cipped direct

On a perforated cable tray or Free air

 

 

Free air

2 cables,

Single-Phase

 a.c. or d.c.

3 or 4 cables

 three-phase a.c.

2 cables,

Single-Phase

 a.c. or d.c.

3 or 4 cables

three-phase a.c.

2 cables,

Single-Phase a.c. or d.c. flat and touching

3 or 4 cables

three-phase a.c.

flat and touching or trefoil

2 cables,

Single-Phase a.c. or d.c. flat and touching

3 or 4 cables

 three-phase a.c. flat and touching or trefoil

               

1

2

3

4

5

6

7

8

9

mm2

A

A

A

A

A

A

A

A

1

14.5

13

17

15

19

17

21

18

1.5

18.5

16.5

22

19.5

24

22

26

23

2.5

25

22

30

26

33

30

36

32

4

33

30

40

35

45

40

49

42

6

42

38

51

44

58

52

63

54

10

57

51

69

60

80

71

86

75

16

76

68

91

80

107

96

115

100

25

99

89

119

105

138

119

149

127

35

121

109

146

128

171

147

185

158

50

145

130

175

154

209

179

225

192

70

183

164

221

194

269

228

289

246

95

220

197

265

233

328

278

352

298

120

253

227

305

268

382

322

410

346

150

290

259

334

300

441

371

473

399

185

329

295

384

340

506

424

542

456

240

386

346

459

398

599

500

641

538

300

442

396

532

455

693

576

741

621

400

-

-

625

536

803

667

865

741

Note:   1.   With or without protective conductor.

             2.   For cables in rigid PVC conduit, the value stated in A6(2) are applicable.

     3.   Cirecular conductors are assumed for sizes up to and including 16mm2. Value     for larger sizes related to shaped conductors and may safely be applied to          circular conductors.

     4.   For details, please refer to BS7671:2001 Tale 4E2A

 

VOLTAGE DROP (millivolt per amperes per metre):Conductor operating temperature: 90oC

   Table 5(b)

Conductor Cross-Sectional Area

Two-core cable d.c.

Two core cable single phase a.c.

Three or four-core cable three-phase a.c.

mm2

mV/A/m

mV/A/m

mV/A/m

 

46

46

40

1.5

31

31

27

2.5

19

19

16

4

12

12

10

6

7.9

7.9

6.8

10

4.7

4.7

4.0

16

2.9

2.9

2.5

 

 

r

x

Z

r

x

Z

25

1.85

1.85

0.160

1.90

1.60

0.140

1.65

35

1.35

1.35

0.155

1.35

1.15

0.135

1.15

50

0.98

0.99

0.155

1.00

0.86

0.135

0.87

70

0.67

0.67

0.150

0.69

0.59

0.130

0.60

95

0.49

0.50

0.150

0.52

0.43

0.130

0.45

120

0.39

0.40

0.145

0.42

0.34

0.130

0.37

150

0.31

0.32

0.145

0.35

0.28

0.125

0.30

185

0.25

0.26

0.145

0.29

0.22

0.125

0.26

240

0.195

0.200

0.140

0.24

0.175

0.125

0.21

300

0.155

0.160

0.140

0.21

0.140

0.120

0.185

400

0.120

0.130

0.140

0.190

0.115

0.120

0.165

Note:   1.   For details, please refer to BS7671:2001 Tale 4E2B

 

Correction Factors for Sizing of Cable Conductors

(1)Correction factors for ambient temperature

APPENDIX 1

Table 1(a)

 

Type of insulation

Operating temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

 

General purpose PVC

70oC

1.03

1.0

0.94

0.87

0.79

0.71

0.61

0.50

0.35

-

-

-

-

-

-

 

 

Heat resisting PVC

90oC

1.03

1.0

0.97

0.94

0.91

0.87

0.84

0.80

0.76

0.71

0.61

0.50

0.35

-

-

Thermosetting (XLPE)

90oC

1.02

1.0

0.96

0.91

0.87

0.82

0.76

0.71

0.65

0.58

0.50

0.41

0.29

-

-

 

 

                                     

1.For details, please refer to BS7671:2001 Tale 4C1