Power Cable-Technical Details

 

Multicore armoured XLPE insulated cables current rating

CURRENT CARRYING CAPACITY (Amperes):Ambient temperature: 30oC

                                                                                    Conductor operating temperature: 90oC

APPENDIX 6

Table 6(a)

Conductor Cross-Sectional Area

Open and clipped direct:

On a perforated cable tray horizontal or Vertical

 

 

1 two-core cable single-phase a.c. or d.c

1 three or four-core cable, three-phase a.c.

1 two-core cable single-phase a.c. or d.c

1 threeor four-core cable tray, or reference Method 13(fee air)

Short circuit current for    1 second

   

 

 

 

mm2

A

A

A

A

kA

1.5

27

23

29

25

0.21

2.5

36

31

39

33

0.35

4

49

42

52

44

0.57

6

62

53

66

56

0.85

10

85

73

90

78

1.43

16

110

94

115

99

2.28

25

146

124

152

131

3.57

35

180

154

188

162

5.00

50

219

187

228

197

7.15

70

279

238

291

251

10.01

95

338

289

354

304

13.58

120

392

335

410

353

17.16

150

451

386

472

406

21.45

185

515

441

539

463

26.45

240

607

520

636

546

34.32

300

698

599

732

628

42.90

400

787

673

847

728

57.20

 

VOLTAGE DROP (millvolt per amperes per metre):Conductor operating temperature: 90oC

Table 6(b)

Conductor Cross-Sectional Area

Two-core cable d.c.

Two core cable single phase a.c.

Three or four-core cable three-phase a.c.

mm2

mV/A/m

mV/A/m

mV/A/m

1.5

31

31

27

2.5

19

19

16

4

12

12

10

6

7.9

7.9

6.8

10

4.7

4.7

4.0

16

2.9

2.9

2.5

 

 

r

x

z

r

x

Z

25

1.85

1.85

0.160

1.90

1.60

0.140

1.65

35

1.35

1.35

0.155

1.35

1.15

0.135

1.15

50

0.98

0.99

0.155

1.00

0.86

0.135

0.87

70

0.67

0.67

0.150

0.69

0.59

0.130

0.60

95

0.49

0.50

0.150

0.52

0.43

0.130

0.45

120

0.39

0.40

0.145

0.42

0.34

0.130

0.37

150

0.31

0.32

0.145

0.35

0.28

0.125

0.30

185

0.25

0.26

0.145

0.29

0.22

0.125

0.26

240

0.195

0.20

0.140

0.24

0.175

0.125

0.21

300

0.155

0.16

0.140

0.21

0.140

0.120

0.185

400

0.120

0.13

0.140

0.190

0.115

0.120

0.165

Note: The above current carrying capacities are for reference only, the current carrying capacities may be varied for different installation conditions

Correction Factors for Sizing of Cable Conductors

(1)Correction factors for ambient temperature

APPENDIX 1

Table 1(a) 

Type of insulation

Operating temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

 

General purpose PVC

70oC

1.03

1.0

0.94

0.87

0.79

0.71

0.61

0.50

0.35

-

-

-

-

-

-

 

 

Heat resisting PVC

90oC

1.03

1.0

0.97

0.94

0.91

0.87

0.84

0.80

0.76

0.71

0.61

0.50

0.35

-

-

Thermosetting (XLPE)

90oC

1.02

1.0

0.96

0.91

0.87

0.82

0.76

0.71

0.65

0.58

0.50

0.41

0.29

-

-

 

 

                                   

 