Power Cable-Technical Details

Multicore armoured PVC insulated cables current rating
 
 
CURRENT CARRYING CAPACITY (Amperes): Ambient temperature: 30oC
                                                                                       Conductor operating temperature: 70oC
 
APPENDIX 3

Table 3(a) 

Conductor Cross-Sectional Area

Open and clipped direct:

On a perforated cable tray horizontal or Vertical

1 two-core cable single-phase a.c. or d.c

1 three or four-core cable, three-phase a.c.

1 two-core cable single-phase a.c. or d.c

1 threeor four-core cable tray, or reference Method 13(fee air)

       

mm2

A

A

A

A

1.5

21

18

22

19

2.5

28

25

31

26

4

38

33

41

35

6

49

42

53

45

10

67

58

72

62

16

89

77

97

83

25

118

102

128

110

35

145

125

157

135

50

175

151

190

163

70

222

192

241

207

95

269

231

291

251

120

310

267

336

290

150

356

306

386

332

185

405

348

439

378

240

476

409

516

445

300

547

469

592

510

400

621

540

683

590

 

VOLTAGE DROP (millvolt per amperes per metre):Conductor operating temperature: 70oC

Table 3(b) 

Conductor Cross-Sectional Area

Two-core cable d.c.

Two core cable single phase a.c.

Three or four-core cable three-phase a.c.

mm2

mV/A/m

mV/A/m

mV/A/m

1.5

29

29

25

2.5

18

18

15

4

11

11

9.5

6

7.3

7.3

6.4

10

4.4

4.4

3.8

16

2.8

2.8

2.4

 

 

r

x

Z

r

x

Z

25

1.75

1.75

0.170

1.75

1.50

0.145

1.50

35

1.25

1.25

0.165

1.25

1.10

0.145

1.10

50

0.93

0.93

0.165

0.94

0.80

0.140

0.81

70

0.63

0.63

0.160

0.65

0.55

0.140

0.57

95

0.46

0.47

0.155

0.50

0.41

0.140

0.43

120

0.36

0.38

0.155

0.41

0.33

0.135

0.35

150

0.29

0.30

0.155

0.34

0.26

0.135

0.29

185

0.23

0.25

0.150

0.29

0.21

0.130

0.25

240

0.180

0.190

0.150

0.24

0.165

0.130

0.21

300

0.145

0.155

0.145

0.21

0.135

0.130

0.185

400

0.105

0.115

0.145

0.185

0.100

0.125

0.160

 Note:The above current carrying capacities are for reference only, the current carrying capacities may be varied for different installation conditions

 

Correction Factors for Sizing of Cable Conductors

(1)Correction factors for ambient temperature

APPENDIX 1

Table 1(a)

Type of insulation  

Operating temperature

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

 

General purpose PVC

70oC

1.03

1.0

0.94

0.87

0.79

0.71

0.61

0.50

0.35

-

-

-

-

-

-

 

 

 

Heat resisting PVC

90oC

1.03

1.0

0.97

0.94

0.91

0.87

0.84

0.80

0.76

0.71

0.61

0.50

0.35

-

-

Thermosetting (XLPE)

90oC

1.02

1.0

0.96

0.91

0.87

0.82

0.76

0.71

0.65

0.58

0.50

0.41

0.29

-

-

 

 

 

 