Table 3(a)
|
Conductor
Cross-Sectional Area |
Open
and clipped direct: |
On
a perforated cable tray horizontal or Vertical |
||
|
|
|
|||
|
1
two-core cable single-phase a.c. or d.c |
1
three or four-core cable, three-phase a.c. |
1
two-core cable single-phase a.c. or d.c |
1
threeor four-core cable tray, or reference Method 13(fee air) |
|
|
mm2 |
A |
A |
A |
A |
|
1.5 |
21 |
18 |
22 |
19 |
|
2.5 |
28 |
25 |
31 |
26 |
|
4 |
38 |
33 |
41 |
35 |
|
6 |
49 |
42 |
53 |
45 |
|
10 |
67 |
58 |
72 |
62 |
|
16 |
89 |
77 |
97 |
83 |
|
25 |
118 |
102 |
128 |
110 |
|
35 |
145 |
125 |
157 |
135 |
|
50 |
175 |
151 |
190 |
163 |
|
70 |
222 |
192 |
241 |
207 |
|
95 |
269 |
231 |
291 |
251 |
|
120 |
310 |
267 |
336 |
290 |
|
150 |
356 |
306 |
386 |
332 |
|
185 |
405 |
348 |
439 |
378 |
|
240 |
476 |
409 |
516 |
445 |
|
300 |
547 |
469 |
592 |
510 |
|
400 |
621 |
540 |
683 |
590 |
VOLTAGE
DROP (millvolt per amperes per metre):Conductor
operating temperature: 70oC
Table 3(b)
|
Conductor
Cross-Sectional Area |
Two-core
cable d.c. |
Two
core cable single phase a.c. |
Three
or four-core cable three-phase a.c. |
||||
|
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
||||
|
1.5 |
29 |
29 |
25 |
||||
|
2.5 |
18 |
18 |
15 |
||||
|
4 |
11 |
11 |
9.5 |
||||
|
6 |
7.3 |
7.3 |
6.4 |
||||
|
10 |
4.4 |
4.4 |
3.8 |
||||
|
16 |
2.8 |
2.8 |
2.4 |
||||
|
|
|
r |
x |
Z |
r |
x |
Z |
|
25 |
1.75 |
1.75 |
0.170 |
1.75 |
1.50 |
0.145 |
1.50 |
|
35 |
1.25 |
1.25 |
0.165 |
1.25 |
1.10 |
0.145 |
1.10 |
|
50 |
0.93 |
0.93 |
0.165 |
0.94 |
0.80 |
0.140 |
0.81 |
|
70 |
0.63 |
0.63 |
0.160 |
0.65 |
0.55 |
0.140 |
0.57 |
|
95 |
0.46 |
0.47 |
0.155 |
0.50 |
0.41 |
0.140 |
0.43 |
|
120 |
0.36 |
0.38 |
0.155 |
0.41 |
0.33 |
0.135 |
0.35 |
|
150 |
0.29 |
0.30 |
0.155 |
0.34 |
0.26 |
0.135 |
0.29 |
|
185 |
0.23 |
0.25 |
0.150 |
0.29 |
0.21 |
0.130 |
0.25 |
|
240 |
0.180 |
0.190 |
0.150 |
0.24 |
0.165 |
0.130 |
0.21 |
|
300 |
0.145 |
0.155 |
0.145 |
0.21 |
0.135 |
0.130 |
0.185 |
|
400 |
0.105 |
0.115 |
0.145 |
0.185 |
0.100 |
0.125 |
0.160 |
Note:The above current
carrying capacities are for reference only, the current carrying capacities
may be varied for different installation conditions
Correction
Factors for Sizing of Cable Conductors
(1)Correction factors for ambient temperature
APPENDIX 1
Table 1(a)
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||