Table 1(b)
|
Reference Method of insulation |
Correction
Factor |
||||||||||||||||||
|
Number
of Circuit or Multicore Cables |
|||||||||||||||||||
|
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
12 |
14 |
16 |
18 |
20 |
||||||
|
Enclosed or
bunched and clipped direct to a non-metallic surface |
|
|
0.80 |
0.70 |
0.65 |
0.60 |
0.57 |
0.54 |
0.52 |
0.50 |
0.48 |
0.45 |
0.43 |
0.41 |
0.39 |
0.38 |
|||
|
|
|
|
|||||||||||||||||
|
Enclosed layer
clipped to a non-metallic surface |
|
Touching |
0.85 |
0.79 |
0.75 |
0.73 |
0.72 |
0.72 |
0.71 |
0.70 |
- |
- |
- |
- |
- |
- |
|||
|
Spaced1 |
0.94 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
0.90 |
|||||
|
Single layer
multicore on a perforated metal cable tray, vertical or horizontal |
|
Touching |
0.86 |
0.81 |
0.77 |
0.75 |
0.74 |
0.73 |
0.73 |
0.72 |
0.71 |
0.70 |
- |
- |
- |
- |
|||
|
Spaced1,2 |
0.91 |
0.89 |
0.88 |
0.87 |
0.87 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|||||
|
Single layer
multicore on a perforated metal cable tray, touching |
|
Horizontal |
0.90 |
0.85 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|||
|
Vertical
|
0.85 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|||||
|
Single layer
multicore touching on ladder supports |
|
|
0.86 |
0.82 |
0.80 |
0.79 |
0.78 |
0.78 |
0.78 |
0.78 |
0.77 |
- |
- |
- |
- |
- |
|||
Note :
1.‘Spaced’means a clearance between adjacent at least one cables diameter(De).
Where the horizontal
clearance between adjacent cables exceeds 2De, no correction factor need be
applied.
2.
Not applicable to Mineral Insulated Cables. Please refer to Table 4B2
of S7671 for the required correction factors.
3.
For details, please refer to BS7671:2001 Table 4B1